Datasheet

YR20.242
Y-Series
12-28V, 20A, DUAL REDUNDANCY MODULE
3. INPUT AND OUTPUT CHARACTERISTICS
Number of inputs - 2
Number of outputs - 1
Input voltage nom. DC 12-28V ±30%
Input voltage range - 8.4-36.4Vdc
Voltage drop, input to output typ. 60mV at 2x5A, 25°C, see Fig. 3-1
typ. 110mV at 2x10A, 25°C, see Fig. 3-1
typ. 130mV at 2x12A, 25°C, see Fig. 3-1
Input current nom. 2x 0-24A
1)
continuous, ambient temperature < +45°C
nom. 2x 0-20A
1)
continuous, ambient temperature < +70°C
nom. 2x 32.5A
2)
for max. 5 seconds
max. 2x 700A for max. 1ms
Output current nom. 24A continuous, ambient temperature < +45°C
nom. 20A continuous, ambient temperature < +70°C
nom. 32.5A
3)
for max. 5 seconds
max.
26A in overload /short-circuit (voltage < 6V). Ensure that the
sum of input currents does not exceed this value.
Reverse current max. 1mA at 24V, per input, -40°C to +70°C
Reverse voltage max. 40Vdc voltage applied to the output, continuously allowed
Output capacitance typ. 320μF
1) Ensure that the sum of both input currents stays below 24A rsp. 20A.
2) Ensure that the sum of both input currents stays below 32.5A.
3) The average value (R.M.S. value) of the output current must not exceed the values of the continuous output current.
Fig. 3-1 Input to output voltage drop Fig. 3-2 Test setup for voltage drop measurements
Voltage Drop, typ
0mV
5A 15A
25mV
50mV
75mV
100mV
125mV
20A10A
Output:
2x5A2x2.5A
Input:
2x10A2x7.5A
0
0
150mV
25A
2x12.5A
Input / Output Current
60°C
25°C
V
A
Power
Supply
24V, 12A
+
-
V
A
I
1
I
2
U
1
U
2
I
1
I
2
=
U
2
U
1
= Voltage Drop
U
1
=
U
OUT
-
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-24A
YR20.242
Input 1
Input 2
Output
Power
Supply
24V, 12A
+
-
Jul. 2017 / Rev. 1.3 DS-YR20.242-EN All parameters are typical values specified at 24V, 20A output current, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/17