User manual

YR2.DIODE
Y-Series
10-60V, 20A, DUAL DECOUPLING MODULE
Nov 2006 / Rev. 1.0 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/16
13. PROTECTION FEATURES
Output over-current protection not included
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 3.5mm E.g. screws, small parts
Over-temperature protection no
Input transient protection no
Internal input fuse not included
Note: In case of a protection event, audible noise may occur.
14. SAFETY
Input / output separation 200V Epitaxial diode
Class of protection III PE (Protective Earth) connection not mandatory
PE resistance < 0.1Ohm Between housing and PE terminal
15. DIELECTRIC STRENGTH
Fig. 15-1 Dielectric strength
A
Type test 60s 500Vac
Factory test 5s 500Vac
Field test 5s 500Vac
A
ChassisIn- / Output
-
+
Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage
with a slow ramp!
During testing, connect all output and input poles together.
The input and output voltage is floating and has no ohmic connection to ground.