User manual
YR2.DIODE
Y-Series
10-60V, 20A, DUAL DECOUPLING MODULE
Nov 2006 / Rev. 1.0 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
16/16
22.9. MOUNTING ORIENTATIONS
Mounting orientations other than vertical require a reduction in continuous output current or a limitation in the
max. allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply.
Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results approx. in half the lifetime expectancy of A1).
Fig. 22-7
Mounting
Orientation A
Standard
Orientation
Decoupling
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°
C
4
12
16
20A
50
A
1
8
Ambient Temperature
Fig. 22-8
Mounting
Orientation B
(Upside down)
Decoupling
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°
C
4
12
16
20A
50
A
1
8
Ambient Temperature
Fig. 22-9
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°
C
4
12
16
20A
50
8
A
1
A
2
Ambient Temperature
Fig. 22-10
Mounting
Orientation D
(Horizontal cw)
Decoupling
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°
C
4
12
16
20A
50
8
A
1
A
2
Ambient Temperature
Fig. 22-11
Mounting
Orientation E
(Horizontal ccw)
Decoupling
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°
C
4
12
16
20A
50
8
A
1
A
2
Ambient Temperature