10-60V, 20A, DUAL DECOUPLING MODULE
Nov 2006 / Rev. 1.0 DS-YR2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/16
22.3. 1+1 REDUNDANCY UP TO 20A
1+1 Redundancy up to 20A requires two 20A power supplies and two YR2.DIODE decoupling modules.
Fig. 22-2 Wiring diagram, 1+1 Redundancy, 20A output current
L1 L2 L3 PE
+ +
- -
QT20.241
Power
Supply
Adj
Overload
DCok
24V/20A
YR2.Diode
Decoupling
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
L1 L2 L3 PE
+ +
- -
QT20.241
Power
Supply
Adj
Overload
DCok
24V/20A
YR2.Diode
Decoupling
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
Failure
Monitor
20A
Load
I I I
optional
optional
I I I
L1
L2
PE
L3
22.4. N+1 REDUNDANCY, EXAMPLE WITH 20A
N+1 Redundancy with 20A requires three 10A power supplies and two YR2.DIODE decoupling modules.
Please note:
The DC-ok signal on the DIMENSION Q-Series will only work properly if the adjusted output voltage of each power
supply will be reached after turning-on the input power. A power supply operating in current limiting mode will result
in a DC-fail condition. Read notes in the individual power supply datasheets.
Fig. 22-3 Wiring diagram, N+1 Redundancy, example with 20A load current
YR2.Diode
Decoupling
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
L N PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V/10A
L N PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V/10A
Failure
Monitor
20A
Load
optional
I I
L
N
PE
YR2.Diode
Decoupling
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
L N PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V/10A
I