22. APPLICATION NOTES
22.1. RECOMMENDATIONS FOR REDUNDANCY
Recommendations for the configuration of redundant power systems:
Use separate input fuse for each power supply.
It is desirable to set the output voltages of all power supplies to the same value to avoid a false signal of the
DC-ok signal.
Use Three-phase power supplies to gain functional safety if one phase fails.
When Single-phase power supplies are utilized connect them to different phases or mains circuits.
Use both inputs in parallel for currents above 10A.
22.2. 1+1 REDUNDANCY UP TO 10A
1+1 Redundancy up to 10A requires two 10A power supplies and one YR2.DIODE decoupling module.
Fig. 22-1 Wiring diagram, 1+1 Redundancy, 10A output current
YR2.Diode
Decoupling
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
L N PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V/10A
L N PE
+ +
- -
QS10.241
Power
Supply
Adj
Overload
DCok
24V/10A
Failure
Monitor
10A
Load
optional
I I
L
N
PE