Datasheet

UF20.241
U-Series
24V, 20A, 200ms
Dec 2005 / Rev. 1.2 / DS-UF20.241-EN / All parameters are specified at 24V, 20A and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/11
16. PROTECTION FEATURES
Buffer protection Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
in buffer mode
typ. 32Vdc
max. 35Vdc
In case of an internal defect, a redundant circuitry
limits the maximum output voltage. The output shuts-
down and makes restart attempts automatically.
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 3.5mm e.g. screws, small parts
Reverse polarity protection yes max. –35Vdc
Input over-voltages protection yes max. 35Vdc, no harm or defect of the unit
Internal fuse not included
17. SAFETY
Output voltage SELV IEC/EN 60950-1
PELV EN 60204-1, EN 50178, IEC 60364-4-41
Class of protection II
Isolation resistance > 5MOhm Power port to housing, 500Vdc
PE resistance < 0.1Ohm between housing and chassis ground terminal
Dielectric strength 500Vac Power port to signal port
500Vac Power port / signal port to housing
18. APPROVALS
UL 508
IND. CONT. EQ.
18WM
LISTED E198865 listed for use in U.S.A. (UL 508) and
Canada (C22.2 No. 14-95)
Industrial Control Equipment
UL 60950-1
RECOGNIZED E137006 recognized for the use in
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950)
Information Technology Equipment, Level 5
IEC 60950-1
IECEE
CB SCHEME
CB Scheme,
Information Technology Equipment
19. FULFILLED STANDARDS
EN/IEC 60204-1 Safety of Electrical Equipment of Machines
EN/IEC 61131 Programmable Controllers
EN 50178 Electronic Equipment in Power Installations