The signal port (active and ready signal and inhibit input) is floating and separated from the supply voltage.
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all poles of the
power port terminals together as well as all poles of the signal port before conducting the test. When testing, set the
cut-off current settings to the value in the table below. The following isolation tests were performed:
Fig. 21-1 Dielectric strength
A B C
Supply
Voltage
Chassis
Active and Ready Signal
Inhibit Input
A
CB
Type test 60s 500Vac 500Vac 500Vac
Factory test 5s 500Vac 500Vac 500Vac
Field test 5s 500Vac 500Vac 500Vac
Cut-off current setting > 1mA > 1mA > 1mA
22. A
PPROVALS
E
U Declaration of Conformity
The CE mark indicates conformance with the EMC directive
IEC
60950-1
2
nd
Edition
CB Scheme,
Information Technology Equipment
UL 60950
-1
2
nd
Edition
Recognized for use as Information Technology Equipment,
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1);
E-File: E137006
UL 508
IND. CONT. EQ.
Listed for use as Industrial Control Equipment;
U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01);
E-File: E198865