Data Sheet
UC10.241, UC10.242
UC-Series 
24V, 15A, CAPACITOR-BASED DC-UPS 
7.  READY AND BUFFERING RELAY CONTACT 
The DC-UPSs are equipped with two independent relay contacts for remote monitoring and controlling of the unit. 
Ready contact 
Contact is closed when capacitor is completely charged, input voltage is sufficient and inhibit signal is not active. 
Contact ratings  max.  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A 
resistive load 
 min. 1mA at 5Vdc  min. permissible load 
Isolation voltage  500Vac, signal port to power port 
Buffering contact 
Contact is closed when unit is buffering. 
Contact ratings  max.  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A 
resistive load 
 min. 1mA at 5Vdc  min. permissible load 
Isolation voltage  500Vac, signal port to power port 
8.  INHIBIT INPUT 
The inhibit input disables buffering. In normal mode, a static signal is required. In buffer 
mode, a pulse with a minimum length of 250ms is required to stop buffering. The inhibit 
is stored and can be reset by cycling the input voltage. See also section 23.7 for 
application notes. 
7
+
5.1V
3mA
Inhibit
8
-
Signal voltage  max.  35Vdc 
Signal current  max.  6mA, current limited 
Inhibit threshold  min. 
max. 
6Vdc, buffering is disabled above this threshold level 
10Vdc 
Isolation voltage  500Vac, signal port to power port 
May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 
9/27