Data Sheet
UC10.241, UC10.242
UC-Series 
24V, 15A, CAPACITOR-BASED DC-UPS 
Notes for use in hazardous location areas: 
The DC-UPS is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 
2) environments and are evaluated according to EN 60079-0 and EN 60079-15. 
WARNING EXPLOSION HAZARDS! 
Substitution of components may impair suitability for this environment. Do not disconnect the unit or change unit 
settings unless power has been switched off or the area is known to be non-hazardous. 
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the 
requirements of the EN 60079-15. 
3.  INPUT 
Input voltage  nom.  DC 24V 
-20%/+25%
Input voltage ranges  typ. 
max. 
22.5 to 30Vdc 
30 to 35Vdc 
continuous operation 
temporarily allowed, no damage to the unit 
Between 30 and 35Vdc buffering is not possible, the 
unit indicates “Check Input Voltage” with the red LED 
on the front 
Transfer threshold voltage   
typ. 
typ. 
max. 
22.45V 
±1% 
22.55V
22.60V 
22.88V 
at no load 
at 10A buffer current 
at 15A buffer current 
at 15A buffer current 
The transfer threshold voltage describes the input 
voltage, where the unit switches into buffer mode and 
delivers output voltage from the capacitors if the input 
was above the turn-on level before and all other buffer 
conditions are fulfilled. 
Turn-on voltage  typ. 
max. 
22.8Vdc 
23.0V 
The output does not switch on if the input voltage is 
below this level. 
Allowed voltage between input 
and earth (chassis) 
max. 60Vdc or 
42.4Vac 
continuous, IEC 62103 
Current consumption  typ.  0.09A  capacitors charged, output current not included 
typ. 
max. 
1.1A 
1.3A 
during charging, output current not included
Input current  max.  17A  during charging an full output current 
Return current  typ. 
max. 
-9mA 
-11mA 
Leakage current to input in buffer mode 
Suitable power sources on 
input 
no limitation in the maximum power supply current 
  Fig. 3-1 Input voltage range    Fig. 3-2 Current budget 
4/27
V
OUT
A: Buffer mode
B: Normal mode
C: Short-term, no harm to the unit
V
IN
18 30 35V22.50
ABC
Internal
current
consumption
Current
consumption
for capacitor
charging
Output
Current
Input
Current
May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 