Data Sheet
UC10.241, UC10.242
UC-Series 
24V, 15A, CAPACITOR-BASED DC-UPS 
16. ENVIRONMENT 
Operational temperature 
*)  -40°C to +60°C (-40°F to 140°F)   
Storage temperature  -40 to +70°C (-40°F to 158°F)  for storage and transportation 
Humidity 
**)  5 to 95% r.H.  IEC 60068-2-30 
Vibration sinusoidal  2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 
***)
2 hours / axis 
IEC 60068-2-6 
Shock  30g 6ms, 20g 11ms 
***)
3 bumps / direction, 18 bumps in total 
IEC 60068-2-27 
Altitude  0 to 6000m (0 to 20 000ft)  Approvals apply only up to 2000m 
Over-voltage category  II  IEC 62103, EN 50178, EN 60950, UL 840 
Degree of pollution  2  IEC 62103, EN 50178, not conductive 
LABS compatibility  The unit does not release any silicone or other LABS-critical substances and is suitable for 
use in paint shops. 
*)  Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the 
unit. 
**) Do not energize while condensation is present 
***) Higher levels allowed when using the wall mounting bracket ZM2.WALL 
  Fig. 16-1 Output current vs. ambient temp.     
0
-40 0 +40
+60°C
2.5
5.0
7.5
10.0
12.5
15A
Ambient Temperature
Allowable Output Current
May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 
17/27