Data Sheet
UC10.241, UC10.242
UC-Series 
24V, 15A, CAPACITOR-BASED DC-UPS 
15. EMC 
The DC-UPS is suitable for applications in industrial environment as well as in residential, commercial and light industry 
environment without any restrictions. 
EMC Immunity 
According generic standards: EN 61000-6-1 and EN 61000-6-2 
Electrostatic discharge  EN 61000-4-2  contact discharge *) 
air discharge *) 
8kV 
15kV 
Criterion A 
Criterion A 
Electromagnetic RF field  EN 61000-4-3  80MHz-2.7GHz  10V/m  Criterion A 
Fast transients (Burst) EN 61000-4-4 input lines 
output lines 
signals **) 
2kV 
2kV 
2kV 
Criterion A 
Criterion A 
Criterion A 
Surge voltage on input  EN 61000-4-5  + Æ - 
+ / - Æ chassis ground 
500V 
1kV 
Criterion A 
Criterion A 
Surge voltage on output  EN 61000-4-5  + Æ - 
+ / - Æ chassis ground 
500V 
1kV 
Criterion A 
Criterion A 
Surge voltage on inhibit 
input, ready- and buffering 
contacts and PC-mode 
selector 
EN 61000-4-5  signals Æ chassis ground  1kV  Criterion A 
Conducted disturbance  EN 61000-4-6 0.15-80MHz  10V  Criterion A 
*)  Chassis ground connection earthed (grounded) 
**)  Tested with coupling clamp 
Criterions: 
A:  DC-UPS shows normal operation behavior within the defined limits. 
EMC Emission 
According generic standards: EN 61000-6-3 and EN 61000-6-4 
Conducted emission  IEC/CISPR 16-1-2, IEC/CISPR 16-2-1  input lines  limits for DC power ports acc. 
EN 61000-6-3 fulfilled 
  IEC/CISPR 16-1-2, IEC/CISPR 16-2-1  output lines  limits for DC power ports acc. 
EN 61000-6-3 fulfilled 
Radiated emission  EN 55011, EN 55022    Class B 
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
Switching Frequencies 
The unit has two converters with two different switching frequencies and one switch-
mode current limiter included. 
Switching frequency 1  100kHz  Boost Converter (active only in buffer mode) 
Switching frequency 2  78kHz  Electronic output current limitation 
Switching frequency 3  19.5kHz  Charger 
May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 
16/27