Data Sheet
UC10.241, UC10.242
UC-Series 
24V, 15A, CAPACITOR-BASED DC-UPS 
13. TERMINALS AND WIRING 
The terminals are IP20 finger safe constructed and suitable for field and factory wiring. 
Input and output  Signals 
Type 
bi-stable quick-connect spring-clamp terminals  pluggable spring-clap terminals 
Solid wire  max. 6mm
2
 max. 1.5mm
2
Stranded wire  max. 4mm
2
 max. 1.5mm
2
American Wire Gauge  AWG 20-10  AWG 24-14 
Max. wire diameter  2.8mm (including ferrules)  1.5mm (including ferrules) 
Wire stripping length  10mm / 0.4inch  8mm / 0.3inch 
Screwdriver -  2.5mm slotted 
Fig. 13-1   Connecting a wire 
Instructions: 
a)  Use appropriate copper cables that are designed for 
minimum operating temperatures of: 
60°C for ambient up to 45°C and 
75°C for ambient up to 60°C and 
90°C for ambient up to 70°C minimum. 
b)  Follow national installation codes and installation 
regulations! 
c)  Ensure that all strands of a stranded wire enter the 
terminal connection! 
d)  Unused terminal compartments should be securely 
tightened or closed. 
e)  Ferrules are allowed. 
1. 
Insert the wire
2. 
Close the lever
14/27
To disconnect wire:
reverse the procedure
May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 










