Data Sheet
UC10.241, UC10.242
UC-Series
24V, 15A, CAPACITOR-BASED DC-UPS
10. EFFICIENCY AND POWER LOSSES
Efficiency typ. 97.8% Normal mode, 10A output current, capacitor fully
charged
typ. 97.8% Normal mode, 15A output current, capacitor fully
charged
Power losses typ. 2.9W Normal mode, 0A output current, capacitor fully charged
typ. 4.6W Normal mode, 10A output current, capacitor fully
charged
typ. 7.7W Normal mode, 15A output current, capacitor fully
charged
typ. 5.0W During charging, 0A output current
Fig. 10-1 Efficiency vs. output current in
normal mode, typ.
Fig. 10-2 Power losses vs. output current in
normal mode, typ.
Power losses versus output
current in normal mode
0
Efficiency vs. output
current in normal mode
94.5
07.5
2
5
15A
3
4
7
8W
Ou
t
p
u
t
C
u
r
r
e
n
t
2.5 5 10 12.5
1
6
39
95.5
96.0
97.0
15A
95.0
96.5
97.5
98%
Ou
t
p
u
t
C
u
r
r
e
n
t
5 7 11 13
May 2016 / Rev. 2.2 DS-UC10.241-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/27