18. ENVIRONMENT
Operational temperature 0°C to +40°C (32°F to 104°F) Full output power
Storage temperature -20°C to +50°C (-4°F to 122°F) Storage and transportation
Humidity 5 to 95% r.H. IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 1g *) IEC 60068-2-6
Shock 15g 6ms, 10g 11ms *) IEC 60068-2-27
Altitude 0 to 6000m Approvals apply only up to 2000m
Over-voltage category III EN 50178
II EN 50178 above 2000m altitude
Degree of pollution 2 EN 50178, not conductive
*) Use wall mounting accessory for higher values.
Fig. 18-1 Normal Mode: Output current vs.
ambient temperature
Fig. 18-2 Buffer Mode: Output current vs.
ambient temperature
Allowable Output
Current in Normal Mode
0
01020
60°C
2.5
5
7.5
10
12.5
15A
c
o
n
t
i
n
u
o
u
s
Ambient Temperature
30 40 50
Allowable Output
Current in Buffer Mode
0
01020
60°C
2.5
5
7.5
10
12.5
15A
c
o
n
t
i
n
u
o
u
s
Ambient Temperature
f
o
r
t
y
p
.
5
s
30 40 50
The ambient temperature is defined 2cm below the unit.
19. PROTECTION FEATURES
Output protection Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
in buffer mode
typ. 32Vdc
max. 35Vdc
In case of an internal defect, a redundant circuitry
limits the maximum output voltage. The output
automatically shuts-down and makes restart attempts.
Degree of protection IP20 EN/IEC 60529
Penetration protection > 3.5mm E.g. screws, small parts
Reverse battery polarity protection yes Max. –35Vdc;
Wrong battery voltage protection yes Max. +35Vdc (e.g. 24V battery instead of 12V battery)
Battery deep discharge protection yes The limit is battery current dependent
Over temperature protection yes Output shut-down with automatic restart
Input over-voltage protection yes Max. 35Vdc, no harm or defect of the unit
Internal input fuse 25A, blade type No user accessible part, no service part