Data Sheet
UB20.241
UB-Series 
24V, 20A, DC-UPS 
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 
31/31
23.9.  TROUBLESHOOTING 
The following guidelines provide instructions for fixing the most common failures and problems. Always start with the 
most likely and easiest to check condition. Some of the suggestions may require special safety precautions. See notes in 
section 3 first. 
Symptom: Explanation / Action: 
Single flash on the “Error” LED  -  Check input voltage. 
The input voltage must be at least 1V higher than the selected buffer 
voltage and smaller than 30V. 
“Error” LED is solid on  -  Check correct wiring between the battery and the DC-UPS 
-  Check battery fuse. Is the battery fuse inserted or blown? 
-  Check battery voltage (must be between 14.8V and 30V) 
- Check battery polarity 
DC-UPS did not buffer  -  Inhibit input was set. 
-  Battery did not have enough time to get charged and the battery 
voltage is still below the deep-discharge protection level. 
DC-UPS stopped buffering  -  Deep discharge protection stopped buffering. Use a larger battery, or 
allow sufficient time for charging the battery. 
-  End of service life of the battery 
-  Battery did not have enough time to be charged. 
-  Inhibit input was activated 
-  Buffer time limiter stopped buffering. Change the settings of the buffer 
time limiter on the front of the unit. 
-  At too high temperatures 
DC-UPS stopped buffering for 1s  -  Center-tap connection opens in buffer mode 
- Center-tap connection problems 
DC-UPS constantly switches between 
power supply mode and battery mode 
-  The supplying source on the input is too small and can not deliver 
sufficient current. Use a larger power supply or reduce the output load. 
-  The output voltage of the power supply dips to a too low value. The 
input voltage must always be at least 1V higher than the selected 
buffer voltage and smaller than 30V. 
Increase the output voltage of the power supply 
-  Too high voltage drops on wires. Increase the output voltage of the 
power supply or increase the wires cross section from the power supply 
to the DC-UPS. 










