Data Sheet

UB20.241
UB-Series
24V, 20A, DC-UPS
19. DIELECTRIC STRENGTH
The signal port (relay contacts and inhibit input) are floating and separated from the power port (input voltage,
output voltage, center-tap terminal and temperature sensor).
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all poles of the
power port terminals together as well as all poles of the signal port before conducting the test. When testing, set the
cut-off current settings to the value in the table below. The following isolation tests were performed:
Fig. 19-1 Dielectric strength
A B C
Type test 60s 1060Vac 1060Vac 1060Vac
22/31
Factory test 5s 650Vac 650Vac 650Vac
Field test 5s 500Vac 500Vac 500Vac
Cut-off current setting > 90mA > 1mA > 1mA
Input, Output,
Battery,
Temperature
Sensor,
Center-tap
Chassis
Signal Port
A
CB
20. APPROVALS
EC Declaration of Conformity
The CE mark indicates conformance with the
- EMC directive 2004/108/EC,
- Low-voltage directive (LVD) 2006/95/EC and the
- RoHS directive 2011/65/EU.
IEC 60950-1
2
nd
Edition
CB Scheme,
Information Technology Equipment
Applicable for altitudes up to 2000m.
UL 508
IND. CONT. E
Q.
Listed for use as Industrial Control Equipment;
U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01);
E-File: E198865
UL 60950-1
2
nd
Edition
Recognized for use as Information Technology Equipment,
Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1);
E-File: E137006
Applicable for altitudes up to 2000m.
ANSI / ISA 12.12.01-2013
Class I Div 2
Recognized for use in Hazardous Location Class I Div 2 T4
Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01-2013) and
Canada (C22.2 No. 213-M1987)
Approval for use in hazardous locations Zone 2 Category 3G.
Number of ATEX certificate: EPS 15 ATEX 1 025 X
The DC-UPS must be built-in in an IP54 enclosure.
EN 60079-0, EN 60079-15
ATEX
II 3G Ex nA nC II T4 Gc
Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc
locations. Number of IECEx certificate: IECEx EPS 15.0049X
IEC 60079-0, IEC 60079-15
IECEx
Marine
Germanischer Lloyd classified
Environmental category: C, EMC2
Marine and offshore applications
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany