Data Sheet
UB20.241
UB-Series 
24V, 20A, DC-UPS 
19. DIELECTRIC STRENGTH 
The signal port (relay contacts and inhibit input) are floating and separated from the power port (input voltage, 
output voltage, center-tap terminal and temperature sensor). 
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the 
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all poles of the 
power port terminals together as well as all poles of the signal port before conducting the test. When testing, set the 
cut-off current settings to the value in the table below. The following isolation tests were performed: 
  Fig. 19-1 Dielectric strength   
A B C 
Type test  60s 1060Vac 1060Vac 1060Vac 
22/31
Factory test  5s  650Vac  650Vac  650Vac 
Field test  5s  500Vac  500Vac  500Vac 
Cut-off current setting  > 90mA  > 1mA  > 1mA 
Input, Output,
Battery,
Temperature
Sensor,
Center-tap
Chassis
Signal Port
A
CB
20. APPROVALS 
EC Declaration of Conformity 
The CE mark indicates conformance with the 
- EMC directive 2004/108/EC, 
- Low-voltage directive (LVD) 2006/95/EC and the 
- RoHS directive 2011/65/EU. 
IEC 60950-1 
2
nd
 Edition 
CB Scheme, 
Information Technology Equipment 
Applicable for altitudes up to 2000m. 
UL 508 
IND. CONT. E
Q.
Listed for use as Industrial Control Equipment; 
U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01); 
E-File: E198865 
UL 60950-1 
2
nd
 Edition 
Recognized for use as Information Technology Equipment, 
Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1); 
E-File: E137006 
Applicable for altitudes up to 2000m. 
ANSI / ISA 12.12.01-2013 
Class I Div 2 
Recognized for use in Hazardous Location Class I Div 2 T4 
Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01-2013) and 
Canada (C22.2 No. 213-M1987) 
Approval for use in hazardous locations Zone 2 Category 3G. 
Number of ATEX certificate: EPS 15 ATEX 1 025 X 
The DC-UPS must be built-in in an IP54 enclosure. 
EN 60079-0, EN 60079-15 
ATEX 
II 3G Ex nA nC II T4 Gc
Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc 
locations. Number of IECEx certificate: IECEx EPS 15.0049X 
IEC 60079-0, IEC 60079-15 
IECEx 
Marine 
Germanischer Lloyd classified 
Environmental category: C, EMC2 
Marine and offshore applications 
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 