Data Sheet
UB20.241
UB-Series 
24V, 20A, DC-UPS 
16. ENVIRONMENT 
Operational temperature 
*)  -40°C to +70°C (-40°F to 158°F)  Reduce continuous output current according 
Fig. 16-1. 
The operational temperature range can be 
reduced by the battery specification. The DC-
UPS includes some safety features which 
reduce the temperature range for charging. 
See chapter 5 for details. 
Derating  2.5%/°C  +60°C to +70°C (140°F to 158°F) 
Storage temperature  -40 to +70°C (-40°F to 158°F)  For storage and transportation 
Humidity **)  5 to 95% r.H.  IEC 60068-2-30 
Vibration sinusoidal  2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 
***)
2 hours / axis 
IEC 60068-2-6 
Shock  30g 6ms, 20g 11ms 
***)
3 bumps / direction, 18 bumps in total 
IEC 60068-2-27 
Altitude  0 to 6000m (0 to 20 000ft)  Approvals apply only up to 2000m 
Over-voltage category  II  IEC 62103, EN 50178, EN 60950, UL 840 
Degree of pollution  2  IEC 62103, EN 50178, not conductive 
LABS compatibility  The unit does not release any silicone or other LABS-critical substances and is suitable for 
use in paint shops. 
*)  Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the 
unit. 
**)  Do not energize while condensation is present 
***) Higher levels are allowed when using the wall mounting bracket ZM2.WALL 
Fig. 16-1 Continuous output current vs. 
ambient temp. 
0
-40 0 40
60
5
10
15
20
25A
Ambient Temperature
70°C
a
b
   Power Supply Mode
   Battery Mode
a
b
20-20
Allowable Continuous Output Current
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 