Data Sheet

UB20.241
UB-Series
24V, 20A, DC-UPS
16. ENVIRONMENT
Operational temperature
*) -40°C to +70°C (-40°F to 158°F) Reduce continuous output current according
Fig. 16-1.
The operational temperature range can be
reduced by the battery specification. The DC-
UPS includes some safety features which
reduce the temperature range for charging.
See chapter 5 for details.
Derating 2.5%/°C +60°C to +70°C (140°F to 158°F)
Storage temperature -40 to +70°C (-40°F to 158°F) For storage and transportation
Humidity **) 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
***)
2 hours / axis
IEC 60068-2-6
Shock 30g 6ms, 20g 11ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 6000m (0 to 20 000ft) Approvals apply only up to 2000m
Over-voltage category II IEC 62103, EN 50178, EN 60950, UL 840
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the
unit.
**) Do not energize while condensation is present
***) Higher levels are allowed when using the wall mounting bracket ZM2.WALL
Fig. 16-1 Continuous output current vs.
ambient temp.
0
-40 0 40
60
5
10
15
20
25A
Ambient Temperature
70°C
a
b
Power Supply Mode
Battery Mode
a
b
20-20
Allowable Continuous Output Current
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
20/31