Data Sheet

UB20.241
UB-Series
24V, 20A, DC-UPS
15. EMC
The DC-UPS is suitable for applications in industrial environment as well as in residential, commercial and light industry
environment without any restrictions.
All tests are performed in power supply and battery mode.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge EN 61000-4-2 contact discharge *)
air discharge *)
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 input lines
output lines
signals **)
2kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 + Æ -
+ / - Æ chassis ground
1kV
2kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ chassis ground
1kV
2kV
Criterion A
Criterion A
Surge voltage on battery
and center-tap
EN 61000-4-5 + Æ -
+ / - Æ chassis ground
- ***)
1kV
Criterion A
Criterion A
Surge voltage on inhibit
input, ready-, buffering
and replace battery
contacts
EN 61000-4-5 signals Æ chassis ground 1kV Criterion A
Surge voltage on
temperature sensor
EN 61000-4-5 signals Æ chassis ground 1kV Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
*) Chassis ground connection earthed (grounded)
**) Tested with coupling clamp
***) Not relevant due to short wire length
Criterions:
A: DC-UPS shows normal operation behavior within the defined limits.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 input lines limits for DC power ports acc.
EN 61000-6-3 fulfilled
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 output lines limits for DC power ports acc.
EN 61000-6-3 fulfilled
-
***)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 battery lines
Radiated emission EN 55011, EN 55022 Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
***) Not relevant due to short wire length
Switching Frequency
The DC-UPS has four converters included, three operate with the same switching
frequency.
100kHz Buck-boost converter and battery charger
45 to 80kHz Auxiliary converter,
switching frequency is input voltage dependent
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.