Data Sheet
UB20.241
UB-Series 
24V, 20A, DC-UPS 
14. FRONT SIDE AND USER ELEMENTS 
Fig. 14-1 Front side 
A Input Terminal (screw terminal) 
B
 Output Terminal (screw terminal) One extra (-) pole for easy grounding. 
The minus-pole is internally hard-wired with the minus-pole of the input and battery 
terminals. 
C
 Signal Connector (8-pole plug connector) comprises the following connections: 
  - Ready relay contact, see chapter 7. 
  - Buffering relay contact, see chapter 7. 
  - Inhibit input signal, see chapter 9 and chapter 23.8. 
  - Replace battery, see chapter 5 and 8. 
D
 Battery Terminal (screw terminal) 
E
  Battery Monitoring Connector (3-pole plug connector)  
- Connection for temperature sensor for battery temperature. See chapter 5 (optional).
- “Center-Tap” connection - middle point of the two batteries See chapter 3 (optional). 
F  Red Error LED – This LED indicates that charging or buffering is not possible. The 
  flashing pattern reports the following reasons: 
  - Check wiring 
  - Insufficient input voltage 
  - Too high temperatures 
  For details see Fig. 14-4. 
G
  Yellow Diagnosis LED – This LED helps troubleshooting and the flashing pattern 
  indicates the following: 
  - Output overloaded (current) 
  - Battery replacement required 
  - Expired buffer time due to buffer time selector or discharged battery 
  - Activated inhibit input 
  For details see Fig. 14-3. 
H
  Green Status LED – Each battery has its own status LED. Battery 1 represents the 
  battery, which is electrically closer to the (+) pole and battery 2, which is closer 
  to the (-) pole. The flashing pattern of this LED reports the following information: 
 - Ready 
 - Charging 
  - Buffering 
  For details see Fig. 14-2. 
I
  Battery Size Selector (pluggable jumper) - For details see chapter 5. 
  Two positions to select battery sizes > and <10Ah. Influences the charging current, the 
  allowed battery temperature range and the battery quality tests. Factory set: <10Ah. 
  A missing jumper equals a <10Ah setting. 
J
 Buffer Time Limiter (rotary switch with 6 dents) - For details see chapter 6. 
  Limits the maximum buffer time in a buffer event to save battery energy. Selectable 
  between 10s 30s, 60s, 3 minutes and 10 minutes. If no limitation is selected (infinite 
  period of time), the buffering will be ended by the deep discharge protection. 
  Factory set: infinite. 
K
  Buffer Voltage Selector (rotary switch with 4 dents) - For details see chapter 4. 
  Allows setting the output voltage in battery mode to 22.5V, 24V, 25V or 26V. 
  Factory set: 22.5V 
L
 Chassis Ground (screw) 
Use a M4 ring-type terminal to connect the housing to ground, when required. 
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 
17/31