Data Sheet
UB20.241
UB-Series 
24V, 20A, DC-UPS 
7.  READY AND BUFFERING RELAY CONTACT 
The DC-UPS is equipped with two independent relay contacts for remote monitoring and controlling of the unit. 
Ready contact 
Contact is closed when both batteries are charged more than typical 85%, no wiring failure is detected, input voltage 
is sufficient and inhibit signal is not active. 
Contact ratings  max.  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A  resistive load 
 min. 1mA at 5Vdc  min. permissible load 
Isolation voltage  see chapter 19. 
Buffering contact 
Contact is closed when unit is in battery mode. 
Contact ratings  max.  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A 
resistive load 
 min. 1mA at 5Vdc  min. permissible load 
Isolation voltage  see chapter 19. 
8.  REPLACE BATTERY RELAY CONTACT 
The contact is closed when one of the battery quality tests of at least one battery reports a negative result. 
To reset the “replace battery” signal, cycle the input power. The battery that has failed is indicated by the green LED 
which is off. The battery should be replaced as soon as possible. 
Contact ratings  max.  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A 
resistive load 
 min. 1mA at 5Vdc  min. permissible load 
Isolation voltage  see chapter 19. 
9.  INHIBIT INPUT 
The inhibit input disables buffering. In power supply mode, a static signal is required. In 
battery mode, a pulse with a minimum length of 250ms is required to stop buffering. See 
chapter 23.8 for details. 
7
+
5.1V
3mA
Inhibit
8
-
Signal voltage  max. 
35Vdc 
Signal current  max.  6mA, current limited 
Inhibit threshold  min. 
max. 
6Vdc, buffering is disabled above this threshold level 
10Vdc 
see chapter 19. Isolation voltage 
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 