Data Sheet
UB20.241
UB-Series 
24V, 20A, DC-UPS 
6.  BUFFER TIME 
The buffer time (sometimes also called autonomy time) is the maximum period of time for which the battery can 
maintain the required output current. The buffer time mainly depends on the capacity and quality of the battery and 
the output current in battery mode. 
The following times are typical values for a new product and the aging effect during operation is not included. 
Pay attention: 
-  The following buffer times apply for a battery temperature between 20°C and 30°C and a buffer voltage setting of 
22.5V. At higher voltages, the buffer time is correspondingly shorter. Furthermore, with a wire length of 2x1m 
(equal 1m cord length) and a cross section of 4mm
2
 (or AWG 12) between the battery module and the DC-UPS. 
-  Due to long-term aging effects of batteries consider a buffer time reduction of 30-50% over time. 
-  The shown buffer times only apply for PULS battery modules or from PULS recommended batteries. 
-  The buffer time is defined for a fully charged battery. The buffer time can be 10-20% shorter for buffer events, 
which start immediately after the “Ready” signal becomes active. 
Battery size 
7Ah 
(UZK24.071) 
12Ah 
(UZK24.121) 
26Ah 
At 22.5V, 0A 
Buffer time  typ.  1d : 17h : 40m : 0s  2d : 22h : 50m : 0s  6d : 19h : 53m : 20s 
At 22.5V, 0.2A 
  typ.  17h : 13m : 20s  1d : 6h : 41m : 40s  2d : 20h : 03m : 20s 
At 22.5V, 1A 
  typ.  5h : 16m : 40s  9h : 51m : 40s  21h : 43m : 20s 
At 22.5V, 2A 
  typ.  2h : 32m : 0s  5h : 17m : 59s  11h : 27m : 30s 
At 22.5V, 5A 
  typ.  46m : 30s  2h : 2m : 55s  4h : 26m : 40s 
At 22.5V, 10A 
  typ.  19m : 11s  46m : 2s  2h : 10m : 0s 
At 22.5V, 15A 
  typ.  10m : 35s  27m : 34s  1h : 17m : 40s 
At 22.5V, 20A 
  typ.  06m : 45s  16m : 47s  55m : 00s 
 typ.  4s  4s  4s 
At 22.5V, 30A 
Battery size 
65Ah  100Ah  140Ah 
At 22.5V, 0A 
Buffer time  typ.  16d : 10h : 26m : 40s  24d : 7h : 20m : 0s  34d : 17h : 20m : 0s 
At 22.5V, 0.2A 
  typ.  7d : 0h : 3m : 20s  10d : 17h : 05m : 0s  14d : 11h : 13m : 20s 
At 22.5V, 1A 
  typ.  2d : 4h : 21m : 40s  3d : 11h : 20m : 0s  4d : 21h : 21m : 40s 
At 22.5V, 2A 
  typ.  1d : 6h : 8m : 20s  1d : 22h : 30m : 0s  2d : 17h : 6m : 40s 
At 22.5V, 5A 
  typ.  11h : 56m : 40s  18h : 30m : 40s  1d : 1h : 55m : 0s 
At 22.5V, 10A 
  typ.  5h : 50m : 15s  9h : 11m : 40s  12h : 52m : 36s 
At 22.5V, 15A 
  typ.  3h : 49m : 17s  6h : 3m : 0s  8h : 27m : 44s 
At 22.5V, 20A 
  typ.  2h : 49m : 29s  4h : 31m : 0s  6h : 19m : 29s 
 typ.  4s  4s  4s 
At 22.5V, 30A 
  Fig. 6-1 Buffer time definition     
Battery
Charge
100%
80-90%
"Ready" signal threshold
t
t
Battery
Mode
Buffer Time
Feb. 2016 / Rev. 2.1 DS-UB20.241-EN 