6. OUTPUT IN NORMAL MODE 
Output voltage in normal mode 
nom.  DC 24V  The output voltage follows the input voltage reduced by 
the input to output voltage drop. 
Voltage drop between input and 
output 
max.  0.3V  At 10A output current, see Fig. 6-1 for typical values 
  max.  0.45V  At 15A output current, see Fig. 6-1 for typical values 
  Ripple and noise voltage  max.  20mVpp  20Hz to 20MHz, 50Ohm *) 
 Output current  nom.  15A Continuously allowed 
  Output power  nom.  360W Continuously allowed 
 Short-circuit current  min.  17.9A  Load impedance 100mOhm, see Fig. 6-2 for typical values 
  max.  21A  Load impedance 100mOhm, see Fig. 6-2 for typical values 
  Capacitive and inductive loads    No limitation   
*)  This figure shows the ripple and noise voltage which is generated by the DC-UPS. The ripple and noise voltage 
might be higher if the supplying source has a higher ripple and noise voltage. 
  Fig. 6-1 Input to output voltage drop, typ.   
Fig. 6-2 Output voltage vs. output current in 
normal mode at 24V input, typ. 
Input to Output
Voltage drop
0
02 10
0.1
0.15
0.25
18A
0.05
0.2
0.3
0.35
0.4V
O
u
t
p
u
t
C
u
r
r
e
n
t
4 6 8 12 14 16
Output Voltage
0
0 5 10 15 20
4
8
12
28V
16
20
24
25A
Output Current