13. RELAY CONTACTS AND INHIBIT INPUT 
The DC-UPS is equipped with relay contacts and signal inputs for remote monitoring and controlling of the unit. 
Relay contacts: 
Ready:  Contact is closed when battery is charged more than 85%, no wiring failure are recognized, input 
voltage is sufficient and inhibit signal is not active. 
Buffering:  Contact is closed when unit is buffering. 
Replace Battery:  Contact is closed when the unit is powered from the input and the battery quality test (SOH test) 
reports a negative result. 
  Relay contact ratings  max  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load 
    min  1mA at 5Vdc min. 
  Isolation voltage  max  500Vac, signal port to power port 
Signal input: 
Inhibit:  The inhibit input disables buffering. In normal mode, a static signal is 
required. In buffer mode, a pulse with a minimum length of 250ms is 
required to stop buffering. The inhibit is stored and can be reset by 
cycling the input voltage. See also section 27.1 for application hints. 
 Signal voltage  max.  35Vdc 
 Signal current  max.  6mA, current limited 
  Inhibit threshold  min.  6Vdc, buffering is disabled above this threshold level 
  max.  10Vdc 
  Isolation  nom.  500Vac, signal port to power port 
7 +
5,1V
3mA
Inhibit
8 -