Datasheet

UB10.241
USeries
24V, 10A, DC-UPS
DC-UPS CONTROL UNIT
Requires Only One 12V Battery for a 24V Output
Stable Output Voltage in Buffer Mode
Superior Battery Management for Longest Battery Life
Comprehensive Diagnostic and Monitoring Functions
Replace Battery Signal Included
Electronically Overload and Short Circuit Protected
50% Power Reserves
Selectable Buffer Time Limiter
3 Year Warranty
1. GENERAL DESCRIPTION
2. SHORT-FORM DATA
Input voltage nom. 24Vdc
range 22.5-30Vdc
Output current min.15A Normal mode
min. 10A Buffer mode
Output voltage typ. 0.23V lower
as input voltage
Normal mode
22.25V Buffer mode, 10A
Allowed batteries 3.9Ah to 40Ah VRLA lead acid
Temperature range -25 to +70°C Operational
Derating 0.43A/°C
+60°C to +70°C
normal mode
Dimensions 49x124x117mm WxHxD
Buffer time (at 10A)
typ. 6’45” 7Ah battery module
typ. 55’ 26Ah batt. module
This uninterruptible power supply (UPS) controller
UB10.241 is an addition to standard 24V power
supplies to bridge power failures or voltage
fluctuations. Expensive downtimes, long restart
cycles and loss of data can be avoided.
The DC-UPS includes a professional battery
management system which charges and monitors
the battery to achieve the longest battery service life
as well as many diagnostic functions that ensure a
reliable operation of the entire system.
A unique feature of the UB10.241 is that only one
12V battery is required to buffer the 24V output.
This makes matching batteries unnecessary and
allows a precise battery charging and testing.
The UB10.241 requires one external 12V battery for
which two preassembled battery modules are
available. A lightweight 7Ah battery which can be
mounted on the DIN-Rail and a 26Ah module that
can be panel mounted for longer buffer times.
In addition to the UB10.241, the UBC10.241 UPS
includes the same controller with an integrated 5Ah
battery.
Typical setup of a DC-UPS system with the UB10.241:
24V
Power
Supply
12V
Battery
UB10.241
24V
DC-UPS
e.g.:
UZK12.xxx
24V
Load
AC
e.g.:
Dimension
DC
e.g.: PLC
3. ORDER NUMBERS
4. MARKINGS
DC-UPS
UB10.241
Standard controller
Accessories UZK12.071
Battery module 12V 7Ah
UZO12.07
Mounting kit w/o battery
IND. CONT. E
Q.
UL 508
UL 60950-1
Class I Div 2
UZK12.261
Battery module 12V 26Ah
UZO12.26
Mounting kit w/o battery
ZM1.WALL
Panel/Wall mount bracket
EMC, LVD
GL
Marine
June. 2010 / Rev. 1.3 DS-UB10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany
1/23

Summary of content (23 pages)