Data Sheet
UB10.241 
U–Series 
24V, 10A, DC-UPS 
Mar. 2019 / Rev. 1.3a DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com Phone +49 89 9278 0 Germany 
9/24 
10. E
FFICIENCY AND 
P
OWER 
L
OSSES
  Efficiency  typ.  97.8%  Normal mode, 10A output current, battery fully charged 
  Power losses  typ.  2.9W  Normal mode, 0A output current, battery fully charged 
    typ.  5.5W  Normal mode, 10A output current, battery fully charged 
    typ.  5.0W  During battery charging, 0A output current 
    typ.  2.1W 
During battery charging, to be added to power losses in 
normal mode, fig.Fig. 10-2 
    typ.  18.5W  Buffer mode, 10A output current 
  Fig. 10-1 Efficiency at 24V, typ.     
Efficiency vs. output
current in normal mode
94.5
3 9
95.5
96.0
97.0
15A
95.0
96.5
97.5
98%
Output Current
5 7 11 13
  Fig. 10-2 Losses at 24V, typ.    Fig. 10-3 Losses, typ. 
Power losses versus output
current in normal mode
0
0 7.5
2
3
5
15A
1
4
6
7
8W
Output Current
2.5
5 10 12.5
Power losses in buffer mode, typ.
0
0
6
5
10
15
20W
O
u
t
p
u
t
C
u
r
r
e
n
t
2 4 8 10A