Data Sheet
UB10.241 
U–Series 
24V, 10A, DC-UPS 
Mar. 2019 / Rev. 1.3a DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com Phone +49 89 9278 0 Germany 
6/24 
8.  B
ATTERY 
I
NPUT
The DC-UPS requires one 12V VRLA battery to buffer the 24V output. 
Battery voltage  nom.  DC 12V  Use one maintenance-free 12V VRLA lead acid battery or 
one battery module which is listed in the chapter 
accessories. 
Battery voltage range 
9.0 – 15.0V 
Continuously allowed, except deep discharge protection 
    max.  35Vdc  Absolute maximum voltage with no damage to the unit 
typ.  7.4V  Above this voltage level battery charging is possible 
  Allowed battery sizes 
min.  3.9Ah   
    max.  40Ah   
  Internal battery resistance 
max.  100mOhm  See individual battery datasheets for this value 
  Battery charging method    CC-CV  Constant current, constant voltage mode 
  Battery charging current (CC-mode)  nom.  1.5A  Independent from battery size,  
max.  1.7A  Corresponding 24V input current see Fig. 8-2 
  End-of-charge-voltage (CV-mode) 
  13.4-13.9V  Adjustable, see chapter 14 
  Battery charging time  typ.  5h *)  For a 7Ah battery 
    typ.  17h *)  For a 26Ah battery 
Battery discharging current **) 
typ.  21A  Buffer mode, 10A output current, 11.5V on the battery 
terminal of the DC-UPS, see Fig. 8-1 for other parameters 
    typ.  0.3A  Buffer mode, 0A output current 
    max.  50µA  At no input, buffering had switched off, all LEDs are off 
typ.  270mA  At no input, buffering had switched off, yellow LED 
shows “buffer time expired” (max. 15 minutes) 
  Deep discharge protection ***) 
typ.  10.5V  At 0A output current 
    typ.  9.0V  At 10A output current 
*)   The charging time depends on the duration and load current of the last buffer event. The numbers in the table represent a 
fully discharged battery. A typical figure for a buffer current of 10A is 3h 20Min. for a 7Ah battery. 
**)  The current between the battery and the DC-UPS is more than twice the output current. This is caused by boosting the 12V 
battery voltage to a 24V level.  This high current requires large wire gauges and short cable length for the longest possible 
buffer time. The higher the resistance of the connection between the battery and the DC-UPS, the lower the voltage on the 
battery terminals which increases the discharging current. See also chapter 25 for  more installation instructions. 
***) To ensure longest battery lifetime, the DC-UPS has a battery deep discharge protection feature included. The DC-UPS stops 
buffering when the voltage on the battery terminals of the DC-UPS falls below a certain value. The yellow LED will show 
“buffer time expired” for a period of 15 minutes after the unit stopped buffering. 
  Fig. 8-1 Battery discharging current  
vs. output current, typ. 
  Fig. 8-2 Required input current vs. input 
voltage for battery charging 
Battery Current
0
0
10
20
5
15
25
30A
2.5 7.5 10 15A12.55
Output Current
Voltage on
battery terminal
of the DC-UPS:
A: 10.5V
B:  11V
C:  12V
A B C
Input Current
0
23
0.5
1.0
0.25
0.75
1.25
1.5A
Input Voltage
24 25 26
28V
max. (battery charging current 1.7A)
27
typ. (battery charging current 1.5A)










