27.3.  USING THE INHIBIT INPUT  
The inhibit input disables buffering. In normal mode, a static signal is required. In buffer mode, a pulse with a 
minimum length of 250ms is required to stop buffering. The inhibit is stored and can be reset by cycling the input 
voltage.  
For service purposes, the inhibit input can also be used to connect a service switch. Therefore, the inhibit signal can 
be supplied from the output of the DC-UPS. 
  Fig. 27-3 Wiring example for inhibit input   
DC-
UPS
UB10.241
IN
24V
OUT
24V
Signal Port
BAT
12V
 Power 
Supply
N L
PE
+ -+ -
Buffered
Load
+
-
+ -+ - +
-
Input
Output
+ -
Inhibit
+
-
12V 
Battery
Service 
Switch
27.4.  TROUBLESHOOTING 
The LEDs on the front of the unit and relay contacts indicate about the actual or elapsed status of the DC-UPS. Please 
see also chapter 14. 
The following guidelines provide instructions for fixing the most common failures and problems. Always start with 
the most likely and easiest-to-check condition. Some of the suggestions may require special safety precautions. See 
notes in section 25 first. 
“Check wiring” LED is on  Check correct wiring between the battery and the DC-UPS 
Check battery fuse. Is the battery fuse inserted or blown? 
Check battery voltage (must be typically between 7.4V and 15.1V) 
Check input voltage (must be typically between 22.8V and 30V) 
Check battery polarity 
DC-UPS did not buffer  Inhibit input was set 
Battery did not have enough time to be charged and is still below the deep discharge 
protection limit. 
DC-UPS stopped buffering  Buffer time limiter stopped buffering  set buffer time limiter to a higher value 
Deep discharge protection stopped buffering  use a larger battery, or allow 
sufficient time for charging the battery 
Output was overloaded or short circuit  reduce load 
Output has shut down  Cycle the input power to reset the DC-UPS 
Let DC-UPS cool down, over temperature protection might have triggered. 
DC-UPS constantly switches between normal mode and buffer mode 
The supplying source on the input is too small and can not deliver sufficient current 
 Use a larger power supply or reduce the output load  