Data Sheet
UB10.241 
U–Series 
24V, 10A, DC-UPS 
Mar. 2019 / Rev. 1.3a DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com Phone +49 89 9278 0 Germany 
17/24 
18. E
NVIRONMENT
Operational temperature  -25°C to +70°C (-13° to +158°F)  For the DC-UPS control unit. 
Keep battery in a cooler environment! 
  Derating  0.43A/°C 
+60°C to +70°C (+140°F to +158°F), 
normal mode see Fig. 18-1 
    0.25A/°C 
+60°C to +70°C (+140°F to +158°F), 
buffer mode see Fig. 18-2 
  Storage temperature  -40 to +85°C (-40° to +185°F)  Storage and transportation, except battery 
Humidity  5 to 95% r.H.  IEC 60068-2-30 
Do not energize while condensation is present 
  Vibration sinusoidal  2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g  IEC 60068-2-6 
Shock 
30g 6ms, 20g 11ms 
IEC 60068-2-27 
  Altitude  0 to 6000m  Approvals apply only up to 2000m 
  Over-voltage category  II  EN 50178 
    II  EN 50178 above 2000m altitude 
  Degree of pollution  2  EN 50178, not conductive 
  Fig. 18-1 Output current vs. ambient temperature    Fig. 18-2 Output current vs. ambient temperature 
Allowable Output
Current in Normal Mode
0
-25 0 20 40 70°C
2.5
5
7.5
10
12.5
15A
continuous
60
Ambient Temperature
Allowable Output
Current in Buffer Mode
0
-25 0 20 40 70°C
2.5
5
7.5
10
12.5
15A
continuous
60
Ambient Temperature
for typ. 5s
The ambient temperature is defined 2cm below the unit. 
19. P
ROTECTION 
F
EATURES
  Output protection  Electronically protected against overload, no-load and short-circuits 
  Output over-voltage protection 
in buffer mode 
typ. 32Vdc 
max. 35Vdc 
In case of an internal defect, a redundant circuitry 
limits the maximum output voltage. The output 
automatically shuts-down and makes restart attempts. 
  Degree of protection  IP20  EN/IEC 60529 
  Penetration protection  > 3.5mm  E.g. screws, small parts 
  Reverse battery polarity protection  yes  Max. –35Vdc;  
  Wrong battery voltage protection  yes  Max. +35Vdc (e.g. 24V battery instead of 12V battery) 
  Battery deep discharge protection  yes  The limit is battery current dependent 
  Over temperature protection  yes  Output shut-down with automatic restart 
  Input over-voltage protection  yes  Max. 35Vdc, no harm or defect of the unit 
  Internal input fuse  25A, blade type  No user accessible part, no service part 