Datasheet

sl5e100 / 041210 1/2
Data sheet
5 A with power boost
SL5.100
Input: AC 230V / 115V
Output: 24V / 5A
Power boost up to 6A
High overload current, no switch-off
Quasi-Wide-Range Input
Robust mechanics and EMC
CUL/CSA-C22.2
EMC and
Low Volt.
UL60950 E137006
UL508 LISTED
IND. CONT. EQ.
No 60950
18 WM, 60°C
Directive
CB
scheme
IEC60950
Input
Efficiency, Reliability etc.*
Construction / Mechanics*
* For further information see data sheets „The SilverLine“, „SilverLine Family
Branches“ and mechanics data sheet
Output
Start / Overload Behaviour
Input voltage AC100-120/200-240 V (switchable), 47-63 Hz
(85-132 VAC / 176-264 VAC, 210-375 VDC,
see also „Output: Continuous Loading“)
Quasi-Wide-Range Input: With the switch in the 230V position the pow-
er-supply unit operates at low and moderate loads (until 3 A) at any in-
put voltage between 95 and 264 V AC (see ’Output’ below).
Note: At DC input, always leave the switch in the 230V position
Input current < 2.6 A (switch in 115V position)
< 1.4 A (switch in 230V position)
DCin at open output typ. 5 mA (preserves battery sources)
Inrush current typ. 15 A at 264 V AC and cold start
To be fused with a 10A, B-type 'circuit-breaker' switch based on the usu-
al thermomagn. overload sensing principle (used anyway to fuse the in-
put lines). In addition, the unit contains an internal fuse (not accessible)
EN 61000-3-2 (harmonic current emissions) is fulfilled
Transient
handling
Transient resistance acc. to VDE 0160 / W2
(750 V / 1.3 ms), for all load conditions.
Hold up time > 37 ms at 196 VAC, 24 V / 5 A
(see Diagram overleaf)
Efficiency typ. 90 % (230 VAC, 24 V / 5 A)
Losses typ. 13,3 W (230 VAC, 24 V / 5 A)
MTBF 520,000 h acc. to Siemensnorm SN 29500
(24 V/5 A, 230 VAC, T
amb
= +40 °C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
Housing dimensions and Weight
W x H x D
Free space for
ventilation
•Weight
64 mm x 124 mm x 102 mm (+ DIN rail)
above/below 25 mm recommended
left/right 15 mm recommended
620 g
Design advantages:
All connection blocks are easy to reach as mounted at the front panel.
Input and output are strictly apart from each other and so cannot be
mixed up (Input below, output above).
Output voltage 24 V DC +5% –1%
Output noise
suppression
Radiated EMI values below EN 61000-6-3, even
when using long, unscreened output cables.
Ambient temperature
range T
amb
Operation: -10°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Derating typ. 3 W/K (at T
amb
=+60°C...+70°C)
Voltage regulation better than 2% Vout overall
Ripple / Noise < 50 mV
PP
, (20 MHz bandw., 50 measurem.)
Overvolt. protection typ. 29 V
Parallel operation yes; current sharing available on request
Power back immunity 26 V
Front panel indicator Green LED, goes out at V
out
<18V
Startup delay typ. 0.1 s
Rise time ca. 5-20 ms, depending on load
Overload Behaviour
Special PULS Over-
load Design (see
diagram overleaf)
20% power boost
no disconnection, no hiccup if overloaded
high overload current (up to 1.9 I
Nom
), Vout
is gradually reduced with increasing current.
6A short-term
, at 45°C or forced cooling
even continuous
Advantages:
High short-circuit current, giving large ’start-up window’: unit starts
reliably even with awkward loads (DC-DC converters, motors).
No ’sticking’ such as can occur with fold-back characteristics
Secondary fuses operate reliably
Continuous loading
(at T
amb
= -10°C...+60°C,
convection cooling), see
also diagram overleaf.
For start at T
amb
< 0°C
and
low input voltage, please
contact PULS.
Output is protected
against short circuit,
open circuit and overload
Switch AC/DCin Iout
230V 176-264 V ACin 5 A / 6 A *
95-176 V ACin 3 A
210-375 V DCin 5 A / 6 A *
150-210 V DCin 3 A
100-150 V DCin 2 A
115V 85-132 V ACin 5 A / 6 A
*
* short-term 6 A (< 1 min), at 45°C or forced cooling
even continuous
Order information
Order number Description
SL5.100
SLR5.100
SLS5.100
SLZ01
(Basic version*)
(N+1 redundancy*)
(Safety Cover*)
Screw mounting set, two needed per unit

Summary of content (2 pages)