Data sheet
2/2 sl20e300 / 031001
Bayerns Best 50
Czech 100 Best
Europe’s 500
Specifications valid for 3 x AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
Construction / Mechanics *
Start / Overload Behaviour
Further Information
Housing dimensions and Weight
•W x H x D
Free space for
ventilation
•Weight
220 mm x 124 mm x 102 mm (+ DIN rail)
above/below 70 mm recommended
left/right 25 mm recommended
1.8 kg
Design advantages:
All connection blocks are easy to reach as mounted at the front panel.
PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
Startup delay typ. 0.2 s
Rise time ca. 20-80 ms, depending on load
Duration of switch-on attempts at
Initial application
on mains
Subsequent
attempts
ca. 1.4 s
ca. 0.5 s
Hiccup operation at V
out
< ca. 14 V
Duration between
switch-on attempts
ca. 4 s
Electronic current limiting, protects against overload and short circuit:
•V
out
< ca. 14 V: Periodical switch-on attempts (hiccup-mode).
•V
out
> ca. 14 V: The output current is continuous.
The V/I characteristic of the supply is straight.
Advantages of the switch-on/overload behaviour:
Safer switch-on into highly non-linear loads with large
starting currents
Short-term overloads result in current limiting and not in
an immediate shut-down.
Parallel operation of several units possible.
Proper switch-on performance is obtained.
For further information, especially about
•EMC
Connections
Safety, Approvals
Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet.
For detailed dimensions
see SilverLine mechanics data sheet SL20
All data is valid for SL20.300.
For SL20.301 (with 480 V input) some values may differ.
0
20
40
60
340 360 380 400 420 440 460 480
Input voltage VACin [V]
Hold-up time [ms]
40% Load
60% Load
80% Load
100% Load
125% Load
84
85
86
87
88
89
90
91
92
93
94
95
4 8 12 16 20 25
Output current Iout [A]
Efficiency [%]
340 V AC
400 V AC
480 V AC
0
8
16
24
32
0 5 10 15 20 25 30 35
Output current Iout [A]
Output voltage Vout [V]
28V / Parallel
28V / Single
24V / Parallel
24V / Single
Vout < ca. 14V: Hiccup mode
Output V/I characteristic (typ.)
Efficiency (typ., at V
out
=24V)
Hold-up time ((typ., at V
out
=24V)