Data sheet
2/2 sl20e300 / 031001
Bayerns Best 50
Czech 100 Best
Europe’s 500
Specifications valid for 3 x AC 400V input voltage, +25°C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change without prior notice.
Construction / Mechanics *
Start / Overload Behaviour
Further Information
Housing dimensions and Weight
•W x H x D
• Free space for
ventilation
•Weight
220 mm x 124 mm x 102 mm (+ DIN rail)
above/below 70 mm recommended
left/right 25 mm recommended
1.8 kg
Design advantages:
• All connection blocks are easy to reach as mounted at the front panel.
• PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
Startup delay typ. 0.2 s
Rise time ca. 20-80 ms, depending on load
Duration of switch-on attempts at
• Initial application
on mains
• Subsequent
attempts
ca. 1.4 s
ca. 0.5 s
Hiccup operation at V
out
< ca. 14 V
Duration between
switch-on attempts
ca. 4 s
Electronic current limiting, protects against overload and short circuit:
•V
out
< ca. 14 V: Periodical switch-on attempts (hiccup-mode).
•V
out
> ca. 14 V: The output current is continuous.
The V/I characteristic of the supply is straight.
Advantages of the switch-on/overload behaviour:
• Safer switch-on into highly non-linear loads with large
starting currents
• Short-term overloads result in current limiting and not in
an immediate shut-down.
• Parallel operation of several units possible.
Proper switch-on performance is obtained.
For further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet.
For detailed dimensions
see SilverLine mechanics data sheet SL20
All data is valid for SL20.300.
For SL20.301 (with 480 V input) some values may differ.
0
20
40
60
340 360 380 400 420 440 460 480
Input voltage VACin [V]
Hold-up time [ms]
40% Load
60% Load
80% Load
100% Load
125% Load
84
85
86
87
88
89
90
91
92
93
94
95
4 8 12 16 20 25
Output current Iout [A]
Efficiency [%]
340 V AC
400 V AC
480 V AC
0
8
16
24
32
0 5 10 15 20 25 30 35
Output current Iout [A]
Output voltage Vout [V]
28V / Parallel
28V / Single
24V / Parallel
24V / Single
Vout < ca. 14V: Hiccup mode
Output V/I characteristic (typ.)
Efficiency (typ., at V
out
=24V)
Hold-up time ((typ., at V
out
=24V)