Datasheet
Your partner in power supply:
European
Power Supply
Manufacturers
Association
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
www.puls-power.com
Fax: +49 89 9278-199
Data sheet
2/2 sl10e110 / 050318
Bayerns Best 50
Czech 100 Best
Europe’s 500
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
All data is valid for the SL20.110. Regarding the SL20.111 (including PFC) some values may differ (please contact us if necessary).
Start / Overload Behaviour
Further information
Startup delay typ. 0.55s
Rise time appr. 20-80ms, depending on load
Overload behaviour
(see characteristic
on the right)
• Power Boost: Short-term (<30s) 125% output
power without voltage drop.
• Electronic current limiting, protects from
overload and short-circuit.
• High overload/short-circuit behaviour
(V
out
<14V) switchable between PULS Over-
load Design and hiccup mode. Switching by
jumper on bottom of the unit; it is not neces-
sary to open the unit for this purpose.
PULS Overload Design™ (continuous current):
• No disconnection/hiccup, thus overloading is possible also for a
longer period of time (load start-up), ideal for parallel operation.
• High overload/short-circuit current due to straight characteristic;
each bias point of the V/I characteristic extends 20A.
Advantage: Due to the high and continuously supplied overload current
the unit starts reliably even with awkward loads (DC-DC converters, mo-
tors). No ’sticking’ such as can occur with fold-back characteristics, and
secondary fuses trigger more reliably.
Hiccup mode:
• Unit switches off when high overload occurs (V
out
< appr. 14V)
with subsequent periodical switch-on attempts (hiccup mode):
– Duration of switch-on attempts:
appr. 0.1s at short-chircuit or appr. 1s at overload
– Duration between switch-on attempts: appr. 1.5s
•V
out
> appr. 14V: The output current is continuous. The V/I charac-
teristic equals that of the PULS Overload Design™; each bias point
of the V/I characteristic extends 20A.
Further information, especially about
•EMC
• Connections
• Safety, Approvals
• Mechanics und Mounting,
see page 2 of the „The SilverLine“ data sheet
For detailed dimensions
see SilverLine mechanics data sheet SL20
0
4
8
12
16
20
24
28
32
0 5 10 15 20 25 30
Output current Iout [A]
Output voltage Vout [
V
28V / Parallel
24V / Parallel
24V / Single
28V / Single
87
88
89
90
91
92
5 10152025
Output current Iout [A]
Efficiency [%]
100 V AC
120 V AC
230 V AC
0
20
40
60
80
80 90 100 110 120 130
Input voltage VACin [V]
Hold-up time [ms]
60% Load
100% Load
125% Load
at 115V AC
0
20
40
60
80
180 190 200 210 220 230 240
Input voltage VACin [V]
Hold-up time [ms]
60% Load
100% Load
125% Load
at 230V AC
Efficiency (typ., at V
out
=24V)
Hold-up time (min., at V
out
=24V)
Output characteristic (typ.)
SL20.110
Vout < appr. 14V: Hiccup mode