Datasheet

QTD20.241
Q-Series
24V, 20A, DC INPUT
3. INPUT
Input nom. DC 600V
-20%/+40%
Input range min. 480-840Vdc Continuous operation
min. 360-480Vdc Maximal 60s or with reduced output current, see Fig. 5-2
min. 840V-900Vdc Maximal 60s or with reduced output current, see Fig. 5-2
max. 1000Vdc Absolute maximum input voltage with no damage to
the DC/DC converter. Above 900Vdc, the output will
switch off and will turn-on again, when the input
voltage falls below 850Vdc.
Allowed voltage input to Earth max. 600V R.M.S. Continuous, IEC 60664-1
max. ±900Vpk Peak value, allowed for transients
Slew rate for voltages between
input and Earth (ground)
max. 1000V/μs
Allowed input ripple voltage max. 50Vpp 50Hz-40kHz
Turn-on voltage typ. 450Vdc Steady-state value, load independent, see Fig. 3-1
Shut-down voltage typ. 325Vdc Steady-state value, load independent, see Fig. 3-1
Input current typ. 0.79A At 24V, 20A, see Fig. 3-3
Start-up delay typ. 350ms See Fig. 3-2
Rise time typ. 70ms At 24V, 20A, only resistive load see Fig. 3-2
typ. 110ms At 24V, 20A, resistive load with an additional 20mF
capacitor
Turn-on overshoot max. 500mV See Fig. 3-2
External capacitors on input Allowed without any limitations
Fig. 3-1 Input voltage range
Turn-on
450Vdc
V
IN
P
OUT
900Vdc
Shut-down
840Vdc
325Vdc
480Vdc
360Vdc
A: continuously allowed
B
: < 60s or with derating
B A
B
Fig. 3-2 Turn-on behavior, definitions Fig. 3-3 Input current vs. output load at 24V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
20A
2 4 6 8 10 12 14 16 18
0
0.2
0.4
0.6
1.0A
0.8
Output Current
Input Current, typ.
Oct. 2016 / Rev. 2.0 DS-QTD20.241-EN
All parameters are specified at 24V, 20A, 600Vdc input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/27