Datasheet

QTD20.241
Q-Series
24V, 20A, DC INPUT
13. EMC
The DC/DC converter is suitable for applications in industrial environment.
EMC Immunity
According to generic standards: EN 61000-6-2 and EN 61800-3
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
DC-OK signal (coupling clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 (+) Æ (-)
(+) / (-) Æ PE
1kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 (+) Æ (-)
(+) / (-)Æ PE
500V
1kV
Criterion A
Criterion A
Surge voltage on DC-OK EN 61000-4-5 DC-OK signal Æ PE 1kV Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
Criterions:
A: DC/DC converter shows normal operation behavior within the defined limits.
EMC Emission
According to generic standards: EN 61000-6-4 and EN 61800-3
Conducted emission
input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 15dB higher than average limits
for DC power port according to
EN 61000-6-4
*)
Conducted emission
output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 5dB higher than average limits
for DC power port according to
EN 61000-6-4
*)
Radiated emission EN 55011, EN 55022 Class A
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) There are no mandatory requirements in the generic standards EN 61000-6-4 and EN 61800-3 for conducted emissions on DC-Lines. For
assessment of the conducted emissions, the input filter of the frequency converter or servo amplifier need to be taken into account.
Switching Frequencies
The DC/DC converter has three converters with three different switching frequencies
included. One is nearly constant. The others are input voltage and load dependent.
Switching frequency 1 100kHz Resonant converter, nearly constant
Switching frequency 2 30kHz to 90kHz Boost converter, load dependent
Switching frequency 3 17kHz to 120kHz Buck converter, input voltage and load dependent