Datasheet
QT40.241, QT40.242
Q-Series
24V, 40A, THREE PHASE INPUT
10. REMOTE CONTROL OF OUTPUT VOLTAGE
The shut-down input can also be used to remotely adjust the output voltage between typically 22Vdc and 28Vdc. All
other functions of shut-down input remain the same.
The control voltage is referenced to the main ground (negative output voltage)
Fig. 10-1 Remote control of the output
voltage
Fig. 10-2 Applying the control voltage
Output Voltage
12V
0V 5V
14V
16V
18V
28V
20V
22V
26V
Control Voltage
24V
10V
Potentiometer:
28V setting
24V setting
15
16
Control
Voltage
min. 0V
max. +50V
Shut-
down
Input
-
+
n.c.
Instructions:
1. Set the unit into “Single Use” mode
2. Set the output voltage adjustment (24-28V) to the maximum desired voltage.
3. Apply a control voltage to reduce the output voltage
Dec. 2016 / Rev. 2.4 DS-QT40.241-EN
All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/29