Datasheet

QS5.241, QS5.241-A1
Q-Series
24V, 5A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks
AC input range min. 85-264Vac continuous operation
min. 60-85Vac full power for 200ms, no damage between 0 and 85Vac
min. 264-300Vac < 500ms
Allowed voltage L or N to earth max. 264Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 82Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 78Vac steady-state value, see Fig. 3-1
typ. 58Vac dynamic value
AC 100V AC 120V AC 230V
Input current typ. 1.34A 1.10A 0.62A at 24V, 5A, see Fig. 3-3
Power factor *) typ. 0.99 0.99 0.91 at 24V, 5A, see Fig. 3-4
Crest factor **) typ. 1.48 1.55 1.71 at 24V, 5A
Start-up delay typ. 120ms 110ms 85ms see Fig. 3-2
Rise time typ. 18ms 18ms 18ms 0mF, 24V, 5A, see Fig. 3-2
typ. 38ms 38ms 38ms 5mF, 24V, 5A, see Fig. 3-2
Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
60V 300Vac264V
Shut-down
full
power
for
200ms
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
5A
0.5 1 1.5 2 2.5 3 3.5 4 4.5
0
0.2
0.4
0.6
0.8
1.0
1.2
1.4A
Output Current
Input
Current, typ.
2
3
0
V
a
c
1
2
0
V
a
c
1
0
0
V
a
c
Power Factor, typ.
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5A
0.75
0.8
0.85
0.9
0.95
1.0
Output Current
100Vac
120Vac
230V
a
c
Nov. 2011 / Rev. 2.1 DS-QS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/26