Datasheet
QS10.301
Q-Series
30V, 8A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks
AC input range min. 85-276Vac continuous operation
min. 60-85Vac full power for 200ms, no damage between 0 and 85Vac
min. 276-300Vac < 500ms
Allowed voltage L or N to earth max. 276Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 81Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 63Vac steady-state value, see Fig. 3-1
typ. 55Vac dynamic value
External input protection See recommendations in chapter 22.4.
AC 100V AC 120V AC 230V
Input current typ. 2.65A 2.22A 1.22A at 30V, 8A, see Fig. 3-3
Power factor *) typ. 0.99 0.98 0.92 at 30V, 8A, see Fig. 3-4
Crest factor **) typ. 1.65 1.67 1.85 at 30V, 8A
Start-up delay typ. 800ms 650ms 340ms see Fig. 3-2
Rise time typ. 21ms 21ms 21ms 0mF, 30V, 8A, see Fig. 3-2
typ. 42ms 41ms 40ms 8mF, 30V, 8A, see Fig. 3-2
Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
4/26
60V 300Vac276V
Shut-down
full
power
for
200ms
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 30V Fig. 3-4 Power factor vs. output load
8A
1234567
0
0.5
1.0
1.5
2.0
2.5
3.0A
Input Current, typ.
Output Current
2
3
0
V
a
c
12
0
V
a
c
10
0Va
c
8A
1234567
0.75
0.8
0.85
0.9
0.95
1.0
Power Factor, typ.
100Vac
120Vac
2
3
0
V
a
c
Output Current
Dec. 2014 / Rev. 2.2 DS-QS10.301-EN
All parameters are specified at 30V, 8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany