Datasheet
QS10.301
Q-Series
30V, 8A, SINGLE PHASE INPUT
Dec. 2014 / Rev. 2.2 DS-QS10.301-EN
All parameters are specified at 30V, 8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22.13. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 22-8
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
INPUT
50
A
1
Ambient Temperature
Fig. 22-9
Mounting
Orientation B
(Upside down)
Power
Supply
26/26
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
A
2
Ambient Temperature
A
1
Fig. 22-10
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
Ambient Temperature
A
1
A
2
Fig. 22-11
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
Ambient Temperature
A
1
A
2
Fig. 22-12
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
Ambient Temperature
A
1
A
2