Datasheet
QS10.301
Q-Series
30V, 8A, SINGLE PHASE INPUT
10. RELIABILITY
AC 100V AC 120V AC 230V
Lifetime expectancy
*) 58 000h 68 000h 71 000h at 30V, 8A and 40°C
117 000h 122 000h 117 000h at 30V, 4A and 40°C
165 000h*) 192 000h*) 200 000h*) at 30V, 8A and 25°C
MTBF
**) SN 29500, IEC 61709 478 000h 535 000h 581 000h at 30V, 8A and 40°C
827 000h 926 000h 1 005 000h at 30V, 8A and 25°C
MTBF
**) MIL HDBK 217F 334 000h 341 000h 345 000h at 30V, 8A and 40°C; Ground
Benign GB40
460 000h 469 000h 474 000h at 30V, 8A and 25°C; Ground
Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
Dec. 2014 / Rev. 2.2 DS-QS10.301-EN
All parameters are specified at 30V, 8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/26