User manual

QS10.121
Q-Series
12V, 15A, SINGLE PHASE INPUT
October 2006 / Rev. 1.0 DS-QS10.121-EN / All parameters are specified at 12V, 15A, 230Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/22
8. OUTPUT
Output voltage
nom. 12V
Adjustment range
min. 12-15V guaranteed, multi turn potentiometer
max. 16.5V at clockwise end position of potentiometer
Factory setting
12.0V
±0.2%,
at full load, cold unit
Line regulation
max. 10mV 60 to 300Vac
Load regulation max. 100mV static value, 0A Æ 15A Æ 0A
Ripple and noise voltage
max. 50mVpp 20Hz to 20MHz, 50Ohm
Output capacitance typ. 7 000µF
Continuous power capability
Output current
nom. 15A at 12V, see Fig. 8-1
nom. 13.5A
at 15V, see
Fig. 8-1
Output power nom. 180W 12V, continuous
nom. 203W 15V, continuous
Short-circuit current
min. 12A load impedance 50mOhm, see Fig. 8-1
max. 18A load impedance 50mOhm, see Fig. 8-1
BonusPower
®
, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or
shutdown. The short-term duration is hardware controlled by an output power manager. The BonusPower
®
is
repeatedly available. Detailed information can be found in chapter 27.1 .
Once BonusPower
®
has been stopped by the output power limiter, a timer disables the next BonusPower
®
capability.
The recovery timer will start as soon as the output voltage reaches the adjusted value again, which usually happens
after the load has been reduced.
Output current
nom. 22.5A at 12V, see Fig. 8-1
nom. 20.3A
at 15V, see
Fig. 8-1
Output power
nom. 270W 12V, short term
nom. 305W 15V, short term
Short-circuit current
min. 15A load impedance 100mOhm, see Fig. 8-1
max. 35A load impedance 100mOhm, see Fig. 8-1
Bonus time typ. 4s at 12V, 22.5A, duration until the output voltage dips,
min 3s see Fig. 8-2
max. 5s
BonusPower
®
recovery time
typ. 7s overload free time to reset power manager, see Fig. 8-3
Peak current capability (up to several ms)
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start
current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will
be discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 27.2.
Peak current voltage dips
typ. from 12V to 10V at 30A for 20ms
typ. from 12V to 7.5V
at 60A for 2ms
typ. from 12V to 5.2V
at 60A for 5ms