Datasheet

QS10.121
Q-Series
12V, 15A, SINGLE PHASE INPUT
10. RELIABILITY
AC 100V AC 120V AC 230V
Lifetime expectancy
*) 61 000h 65 000h 76 000h at 12V, 15A and 40°C
111 000h 117 000h 112 000h at 12V, 7.5A and 40°C
171 000h*) 184 000h*) 215 000h*) at 12V, 15A and 25°C
MTBF
**) SN 29500, IEC 61709 577 000h 582 000h 631 000h at 12V, 15A and 40°C
998 000h 1 006 000h 1 091 000h at 12V, 15A and 25°C
MTBF
**) MIL HDBK 217F 361 000h 362 000h 370 000h at 12V, 15A and 40°C; Ground
Benign GB40
495 000h 496 000h 507 000h at 12V, 15A and 25°C; Ground
Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
Nov. 2011 / Rev. 2.1 DS-QS10.121-EN
All parameters are specified at 12V, 15A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany