User Manual

EN
QS5.DNET Installation Manual
Product Description
The QS5.DNET is a DIN-rail mountable single-phase-input power supply, which provides a floating,
stabilized and galvanically separated SELV/PELV output voltage for the DeviceNet
®
system.
The output of the device is NEC Class 2 compliant and allowed to supply NEC Class 2 circuits.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as in
industrial control, process control, monitoring and measurement equipment or the like. Do not use this
device in equipment where malfunction may cause severe personal injury or threaten human life.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device. Other mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost allowed.
The enclosure of the device provides a degree of protection of IP20.
The isolation of the device is designed to withstand impulse voltages of overvoltage category III
according to IEC 60664-1.
The device is designed as “Class of Protection” I equipment according to IEC 61140.
Do not use without a proper PE (Protective Earth) connection.
The device is suitable to be supplied from TN-, TT- and IT mains networks. The voltage between the L
or N terminal and the PE terminal must not exceed 264Vac continuously.
The input can also be powered from batteries or similar DC sources. The voltage between the input
terminal and the PE terminal must not exceed 375Vdc continuously.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product
datasheet for use above 2000m (6560ft).
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device
is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 30A (UL) and 32A (IEC) without
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A
B- or 3A C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations.
Substitution of components may impair suitability for this environment.
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or
the area is known to be non-hazardous.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including unlimited inductive loads and capacitive loads.
Do not apply return voltages from the load to the output terminals higher than 35V.
The green DC-OK LED reports an output voltage above 21.5V of a running device.
The DC-OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on.
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads.
The red overload LED is on, when the output voltage falls below 21.5V or in case of a short circuit in
the output. The LED is flashing, when the device has switched off due to over-temperature. Input
voltage is required.
The device is equipped with an over-temperature protection. In case of a high temperature, the output
shuts down and starts automatically again after cooling off.
Do not connect outputs of devices in a parallel connection for higher output currents.
Do not connect outputs of devices in a series connection for higher output voltages.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 29V. The output
shuts down and automatically attempts to restart.
Technical Data
All values are typical figures specified at 230Vac 50Hz input voltage, 24V
3.8A output, 25°C ambient temperature and after a 5 minutes run-in time
unless otherwise noted.
Output voltage DC 24V -1.5%/+2.5%
Adjustment range - Not adjustable
Output current 3.8A Below +60°C ambient
3.0A At +70°C ambient
Derate linearly between +60°C and +70°C
Input voltage AC AC 100 - 240V -15%/+10%
Mains frequency 50 – 60Hz ±6%
Input current AC 0.85 / 0.45A At 120 / 230Vac
Power factor 0.98 / 0.90 At 120 / 230Vac
Input voltage DC DC 110 - 300V ±20%
Input current DC 0.91 / 0.33A At 110 / 300Vdc
Input inrush current 9 / 11A pk At 40°C, 120 / 230Vac
Efficiency 91.4 / 92.0% At 120 / 230Vac
Power losses 8.6 / 7.9W At 120 / 230Vac
Hold-up time 44 / 85ms At 120 / 230Vac
Temperature range -25 to +70°C
Max. wire size (litz wire) 4mm² Input terminals
Wire size AWG AWG 20-10 Input terminals
Max. wire diameter 2.8mm Input terminals
Wire stripping length 10mm / 0.4inch Input terminals
Max. wire size (litz wire) 2.5mm² Output/DC-OK terminals
Wire size AWG AWG 26-12 Output/DC-OK terminals
Max. wire diameter 2.3mm Output/DC-OK terminals
Wire stripping length 6mm / 0.25inch Output/DC-OK terminals
Size (wxhxd) 40x124x117mm Without DIN-rail
Weight 620g / 1.37lb
Functional Diagram
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Voltage
Regulator
Power
Converter
Output
Filter
Output
Power
Manager
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter
L
N
DC-OK
Contact
DC-OK
LED
DC-ok
Relay
13
14
Overload
LED
Output Characteristic
Output voltage
5A
24V
Output current
12V
0V
1A 2A 3A 4A0A
Temperature Range
Allowed output current
Ambient temperature
0A
-25
3.8A
0 +70°C
3.0A
+60