Data Sheet
MLY02.100
MiniLine
MLY-Series
DC12-48V, 10A, DUAL REDUNDANCY MODULE
5. RELIABILITY
The redundancy module does not have electrolytic capacitors included. Therefore, the lifetime expectancy and MTBF
value is extremely high.
Input / output
current conditions
Input: 2x5A
Output: 10A
Lifetime expectancy
*) min. 25 years at 24V and 40°C
min. 25 years at 24V and 25°C
MTBF
**) SN 29500, IEC 61709 84 868 000h at 24V 40°C
125 266 000h at 24V 25°C
MTBF
**) MIL HDBK 217F 71 454 000h at 24Vand 40°C (Ground Benign GB40)
81 453 000h at 24Vand 25°C (Ground Benign GB25)
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life).
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
6. TERMINALS AND WIRING
Input and output
Type Bi-stable, quick-connect spring clamp terminals.
IP20 Finger safe construction.
Suitable for field- and factory installation.
Solid wire 0.3-4mm
2
Stranded wire 0.3-2.5mm
2
American Wire Gauge 26-12 AWG
Wire stripping length 6mm / 0.25inch
Pull-out force
10AWG:80N, 12AWG:60N, 14AWG:50N,
16AWG:40N (according to UL486E)
Terminals shipped in open
position.
Fig. 6-1 Connecting a wire
Instructions:
a) The external circuitry of all terminals must meet the safety
requirements stipulated by IEC/EN/UL 60950-1: SELV.
b) Use appropriate copper cables that are designed for
minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.
c) Follow national installation codes and installation
regulations!
d) Ensure that all strands of a stranded wire enter the terminal
connection!
e) Up to two stranded wires with the same cross section are
permitted in one connection point.
f) Ferrules are allowed, but not required.
g) Do not connect or disconnect the wires from the terminals
below -25°C (-13°F).
Oct. 2010 / Rev. 1.0 DS-MLY02.100-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
6/15