18.6. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 18-4
Mounting
Orientation A
(Standard
orientation)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
A
1
4
Ambient Temperature
Fig. 18-5
Mounting
Orientation B
(Upside down)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
A
1
4
Ambient Temperature
Fig. 18-6
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
A
1
A
2
Ambient Temperature
Fig. 18-7
Mounting
Orientation D
(Horizontal cw)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
A
1
A
2
Ambient Temperature
Fig. 18-8
Mounting
Orientation E
(Horizontal ccw)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
A
1
A
2
Ambient Temperature
15/15