18. APPLICATION NOTES
18.1. RECOMMENDATIONS FOR REDUNDANCY
Recommendations for the configuration of redundant power systems:
Use separate input fuses for each power supply.
Use three-phase power supplies to gain functional safety if one phase fails.
When single-phase power supplies are utilized connect them to different phases or mains circuits if possible.
Set the power supply in “Parallel-Use” mode if this feature is available
It is desirable to set the output voltages of all power supplies to the same value.
18.2. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads.
18.3. EXAMPLE: 1+1 REDUNDANCY
1+1 Redundancy up to 2.1A requires two ML50.100 power supplies (each 2.1A output current) and one MLY02.100
redundancy module.
Fig. 18-1 Wiring diagram, 1+1 Redundancy, 2.1A output current
13/15
MLY02.100
IN 1
+
-
+
-
L
N
II
ML50.100
Power
Supply
L N
Output
Input
+ +
- -
DC
OK
IN 2
ML50.100
Power
Supply
L N
Output
Input
Load
+
- -
+
-
Alarm
Monitor
Output
+ +
- -
DC
OK
+
Note: Use separate mains systems for each power supply whenever it is possible
Oct. 2010 / Rev. 1.0 DS-MLY02.100-EN