27.12. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top requires a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output power.
Curve A2 Max allowed output power (results approx. in half the lifetime expectancy of A1).
Fig. 27-8
Mounting
Orientation A
Standard
Orientation
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°
10
30
40
50W
50
A
1
Ambient Temperature
20
Fig. 27-9
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°
10
30
40
50W
50
Ambient Temperature
20
A
1
A
2
Fig. 27-10
Mounting
Orientation C
(Table-top
mounting)
Output Power
0
10 20 30 40
60°
10
30
40
50W
50
Ambient Temperature
20
A
1
A
2
Fig. 27-11
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°
10
30
40
50W
50
Ambient Temperature
20
A
1
A
2
Fig. 27-12
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°
10
30
40
50W
50
Ambient Temperature
20
A
1
A
2