17. ENVIRONMENT
Operational temperature -10°C to +70°C (14°F to 158°F) Reduce output power according to
Fig. 17-1
Output de-rating 1.3W/°C 60-70°C (140°F to 158°F), see
Fig. 17-1
Storage temperature -40 to +85°C (-40°F to 185°F) Storage and transportation
Humidity 5 to 95% r.H. IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock 20g 6ms, 10g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 6000m (0 to 20000ft) Reduce output power or ambient
temperature above 2000m sea level.
Output de-rating (for altitude) 3W/1000m or 5°C/1000m Above 2000m (6500ft), see Fig. 17-2
Over-voltage category III EN 50178, IEC 62103 altitudes < 2000m
II Altitudes from 2000m to 6000m
Degree of pollution 2 EN 50178, IEC 62103, non conductive
Fig. 17-1 Output current vs. ambient temp. Fig. 17-2 Output current vs. altitude, 24V
0
-10 0 20 40
70°
C
0.4
0.8
1.2
1.6
2.0
2.4A
60
Ambient Temperature
Allowable Output
Current at 24V
0
0 2000 4000
6000m
0.4
0.8
1.2
1.6
2.0
2.4A
Altitude
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
A
B
C
Allowable Output
Current at 24V
The ambient temperature is defined 2cm below the unit.
18. PROTECTION FEATURES
Output protection Electronically protected against overload, no-load and short-circuits
Output over-voltage protection typ. 36V
max. 39V
In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Output over-current protection electronically limited see Fig. 10-1
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 2.5mm in diameter E.g. screws, small parts
Over-temperature protection not included
Input transient protection MOV Metal Oxide Varistor
Internal input fuse T3.15A H.B.C. Not user replaceable
Note: In case of a over-voltage, overload, no-load or short-circuit event, an audible noise may be heard.