Datasheet

X Input
Input voltage AC 100-120/220-240V (Auto Select), 47...63 Hz
(AC 85...132V / AC 184...264V,
DC 220...375V, N= + and L= - )
Input current <1.9A (@ AC 100V
in
, 90W P
out
)
<0.9A (@ AC 220V
in
, 90W P
out
)
External fusing not required, unit provides internal fuse
(T3A15H, not accessible)
Transient immunity Transient resistance acc. to VDE 0160 / W2
(750V/ 1.3 ms), over entire load range
Hold-up time
(see diagram below)
>40 ms @ AC 230V, 12V / 7.5A
>20 ms @ AC 196V, 12V / 7.5A
>20 ms @ AC 100V, 12V / 7.5A
X Efficiency, Reliability
Efficiency
Losses
>88.5% (AC 230V, 12V / 7.5A)
(see also diagram below)
<11.7W (AC 230V, 12V / 7.5A)
MTBF (Reliability) appr. 500.000 h acc. to Siemensnorm SN 29500
(12V / 7.5A, AC 230V, T
amb
= +40 °C)
Prior to shipment, every unit undergoes the following tests in order to
isolate any defective units which might suffer an early failure:
Run-in / burn-in (Full load, T
amb
= +60°C, on/off cycle)
Functional test (100 %)
X Construction, Mechanics, Installation
Robust plastic housing (US Patent No. D442, 923S), fine ventilation grid
on three housing sides to keep out small parts (e.g. screws), IP20
Dimensions and weight
W x H x D
•Weight
73 mm x 75 mm x 103 mm (+ DIN rail)
Depth incl. terminals: 98 mm (+ DIN rail)
360 g
Mounting orientation ,
or (cf. ’Output’)
Ventilation/Cooling
Free space f. cooling
Normal convection, no fan required
recom'd.: 25 mm on sides with ventilation grid
Easy snap-on mounting onto the DIN-rail (TS35/7,5 or TS35/15).
Unit sits safely and firmly on the rail; no tools required even to remove
Connection by Spring Clamp terminals; uniformly firm hold,
vibration-resistant and maintenance-free:
2 terminals per output
Connector size range
flexible cable
solid cable
Wire strip length
0.3-2.5mm
2
(28-12 AWG)
0.3-4mm
2
(28-12 AWG)
Ferrules admissible
6mm (0.24in) recommended
X Diagrams
0
2
4
6
8
10
12
14
16
012345678910
Vin = AC 115/230
V
Single Use
Vin = AC 115/230
V
Parallel Use
0,0
20,0
40,0
60,0
80,0
100,0
120,0
140,0
160,0
180,0
80 100 120 140 160 180 200 220 240 260 280
Pout = 90W,typ.
Pout = 90W, mi n.
Pout = 45W, typ.
Pout = 45W, mi n.
0
10
20
30
40
50
60
70
80
90
100
-10 0 10 20 30 40 50 60 70
75
77
79
81
83
85
87
89
91
2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5
230Vac
115Vac
Output characteristic V
out
/I
out
(min.)
Efficiency
Hold-up time with ACin
(@ V
out
= 12V, typ.)
(at V
out
= 12V, typ. + min.)
Derating
of output power
Mounting
85-132 V ACin A-a A-b A-b
184-264 V ACin A-a A-b A-b
220-375 V DCin A-a A-b A-b
a
b
A
Output current lout [A]
Output voltage Vout [V]
Output current lout [A]
Efficiency [%]
Ambient temperature [°C]
Output powwer [W]
Input voltage VACin[V]
Hold-up time [ms]
X Output
Output voltage
preset
DC 12-15V (adj. by front panel potentiometer)
12V ± 0.5% @ 7.5A
Voltage regulation stat. <1.5% V
out
(Jumper in pos. 'Single Use')
stat. <3% V
out
(Jumper in pos. 'Parallel Use'),
dyn. ±2.5% V
out
over all
Ripple/Noise <50mV
PP
(20 MHz bandw., 50 measurement)
Overvoltage prot. (OVP) <18.5V
Rated continuous
loading
up to 7.5A @ 12V/6A @ 15V (convection cooling),
depending on built-in orientation, V
in
and T
amb
For details see derating diagram below
Overload behaviour Straight V/I characteristic (depending on V
in
);
details see diagr. 'output characteristic' below
Protection Unit is protected against (also permanent) short-
circuit, overload and open-circuit.
Derating depending on built-in orientation;
see diagram below
Parallel operation yes (selectable by front panel jumper)
Power back immunity 25V
Operating indicator Green LED
X Environmental Data, EMC, Safety
Ambient temperature range (measured 25 mm below unit)
storage/transport
operation
-25°C ... +85°C
-10°C ... +70°C (for derating see diagram below)
Humidity max. 95% (without condensation)
Electromagnetic
emissions (EME)
EN 61000-6-3 (includes EN 61000-6-4)
Class B (EN 55011, EN 55022)
EN 61000-3-2 (PFC)
Electromagnetic
immunity (EMI)
EN 61000-6-2 (includes EN 61000-6-1)
Safe low voltage:
Prot. class/degree:
SELV (EN 60950, VDE0100/T.410), PELV (EN 50178)
Class 1 (EN 60950) / IP20 (EN 60529)
The PSU complies with all major safety approvals for EU (EN 60 950,
EN 60204-1, EN 50178), USA (UL 60950, E137006, UL508 LISTED, E198865),
Canada (CAN/CSA-C22.2 No 60950 [CUR], CAN/CSA-C22.2 No. 14 [CUL]),
CB Scheme (IEC 60950). Hazardous Location Class I Div. 2 (UL 1604)
Design details – for your advantage:
All terminals are easy to reach as mounted on the front panel.
Input and output are strictly apart from each other (input below, out-
put above) and so cannot be mixed up.
Mounting and connection do not require any screwdriver
Easy, quick, durable and reliable installation.
Technical Data ML100.102
Product information (ML100e102), Rev.: 29. June 2004. Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They
are subject to change without prior notice.
PULS GmbH, Arabellastraße 15, D-81925 München X Tel: +49.(0)89.9278-244, Fax: +49.(0)89.9278-299, E-Mail: sales@puls-power.com X www.puls-power.com
S