12. FRONT SIDE AND USER ELEMENTS
Fig. 12-1
Front side CD5.241
Fig. 12-2
Front side CD5.241-S1
A Output Terminals
Screw terminals (Spring-clamp terminals on the CD5.241-S1)
Dual terminals per pole
+ Positive output
- Negative (return) output
B
Input Terminals
Screw terminals (Spring-clamp terminals on the CD5.241-S1)
+ Positive input
- Negative (return) input
Chassis ground can be used to bond the housing to PE
Ground this terminal to minimize high-frequency emissions.
C
Signal Terminals
Plug Connector for DC-OK and Input-low relay contact
D
Output voltage potentiometer
Open the flap to set the output voltage. Factory set: 24.1V
E DC-OK LED (green) See also chapter 14
CD5.241: On when the voltage on the output terminals is > 21V
CD5.241-S1: Monitors the output voltage, which is produced by
the power supply itself and is on when the voltage is higher
than 90% of the adjusted output voltage.
DC-OK lamp and DC-OK contact functions are synchronized
F
Input-low LED (yellow) See also chapter 15
On when the input voltage is between 4Vdc and 20Vdc..
Input-low LED and Input-low contact functions are synchronized
13. TERMINALS AND WIRING
Input and output
CD5.241
Input and output
CD5.241-S1
Signals
CD5.241-S1
Type Screw terminals Spring-clamp terminals Plug-connector (screws)
Solid wire 0.5-6mm
2
0.5-6mm
2
0.2-1.5mm
2
Stranded wire 0.5-4mm
2
0.5-4mm
2
0.2-1.5mm
2
American wire gauge 20-10 AWG 20-10 AWG 22-14 AWG
Recommended tightening torque 1Nm, 9lb.in - 0.4Nm / 3.5lb.in
Wire stripping length 7mm / 0.275inch 10mm / 0.4inch 6mm / 0.25inch
Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.
b) Follow local and national installation codes and regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point.
e) Ferrules are allowed but not required
f) In order to fulfill GL requirements, unused terminal spaces must be closed.