User manual
CD5.241, CD5.241-S1
CD–Series
DC/DC Converter; 24V, 5A
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/22
7. OUTPUT
Output voltage
nom. 24V
Adjustment range
min. 23-28V Guaranteed
max. 30V At clockwise end position of potentiometer
Factory setting
24.1V
±0.2%,
at full load, cold unit
Line regulation
max.
25mV
Input variations between 18 to 32.4Vdc
Load regulation max. 100mV CD5.241; static value, 0A Æ 5A Æ 0A
max. 150mV CD5.241-S1; static value, 0A Æ 5A Æ 0A
Ripple and noise voltage
max.
50mVpp
20Hz to 20MHz, 50Ohm
Output capacitance typ.
2200µF
Output current nom. 6A At 24V, ambient < 45°C, see Fig. 7-1
nom. 5A
At 24V, ambient < 60°C, see
Fig. 7-1
nom. 5.1A At 28V, ambient < 45°C, see Fig. 7-1
nom. 4.3A
At 28V, ambient < 60°C, see
Fig. 7-1
Output power nom. 144W Ambient < 45°C
nom. 120W
Ambient < 60°C
Short-circuit current
min. 7A Load impedance 200mOhm, see Fig. 7-1
max. 10A Load impedance 200mOhm, see Fig. 7-1
Fig. 7-1 Output voltage vs. output current,
typ. (24Vdc input voltage)
Fig. 7-2 Current limitation vs. input voltage,
typ. (23V constant voltage load)
Output Voltage
0
048
4
8
12
28V
16
20
24
12
A
1062
Adjustment
Range
Output Current
Output Current
5.8
15 21 27
5.9
6.0
6.1
6.6A
6.3
6.4
6.5
33Vdc302418
6.2
Input Voltage
Peak current capability (up to several ms)
The DC/DC converter can deliver a peak current which is higher than the specified short term current. This helps to
start current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the DC/DC converter. During this event, the capacitors
will be discharged and cause a voltage dip on the output. Detailed curves can be found in chapter 27.1.
Peak current voltage dips
typ. from 24V to 18V At 10A for 50ms, resistive load
typ. from 24V to 15V
At 20A for 2ms, resistive load
typ. from 24V to 11.5V
At 20A for 5ms, resistive load