User manual

CD5.241, CD5.241-S1
CDSeries
DC/DC Converter; 24V, 5A
Jan. 08 / Rev. 1.1 DS-CD5.241-EN / All parameters are specified at 24V, 5A and 24Vdc input at 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/22
5. INPUT VOLTAGE
Input
nom. DC 24V
Input voltage range
nom. 18.0-32.4Vdc Continuous operation
14.0-18.0Vdc Max. 60 seconds or with de-rating see Fig. 5-2
max. 36.0Vdc Absolute maximum continuous input voltage with no
damage to the DC/DC converter.
Allowed voltage between input
and earth (ground)
max. 60Vdc or
42.4Vac
Allowed input ripple voltage
max. 5Vpp 47Hz-40kHz, the momentary input voltage must always be
within the specified limits.
Turn-on voltage typ. 17.5Vdc Steady-state value, see Fig. 5-1
Shut-down voltage typ. 14.0Vdc Steady-state value, see Fig. 5-1
typ. 35Vdc Steady-state value, see Fig. 5-1
Input current
typ. 5.5A At 24Vdc input and output 24V, 5A, see Fig. 5-4
Start-up delay typ.
650ms
See Fig. 5-3
Rise time typ. 80ms 0mF, 24V, constant current load 5A, see Fig. 5-3
typ. 150ms 5mF, 24V, constant current load 5A, see Fig. 5-3
Turn-on overshoot
max.
500mV
See Fig. 5-3
Input capacitance typ.
3 000µF
External capacitors on the input voltage bus are allowed without any limitations.
Fig. 5-1 Input voltage range
Fig. 5-2 Allowable output current below 18V
input voltage
Turn-on
17.5Vdc
V
IN
P
OUT
Shut-down
32.4Vdc
14.0Vdc
18.0Vdc
Rated input range
35.0Vdc
0
1
2
3
4
6A
14 16 18 20 24Vdc
Input Voltage
Output Current
5
22
(
a
)
(
b
)
(a) Ambient < 45°C
(b) Ambient < 60°C
Fig. 5-3 Turn-on behavior, definitions Fig. 5-4 Input current vs. output load
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
6A
1
1.5 2 3
4
0
2
4
6
8A
5
Output Current
2.5
3.5
4.5
5.5
I
n
p
u
t
:
2
4
V
d
c
Input
Current,
typ.
I
n
p
u
t
:
1
8
V
d
c